CAN A LOUVER BE INSTALLED IN A FIRE-RATED STEEL DOOR? 

Yes, it is permitted to install a louver in a fire-rated steel door, provided that a specifically approved louver is used and installed according to the manufacturer’s instructions. The louver must be equipped with a certified fusible link that closes automatically the louver in case of heat. Louver installation is permitted for doors with a maximum fire resistance of 90 minutes, with only one louver per leaf, in either a single or double configuration. 

Louvers must be in the lower part of the door, no more than 40 inches (1016 mm) from the floor, with a maximum size of 24″ x 24″ (610 x 610 mm). 

Important Fire Restrictions, not permitted: 

•  In doors with a 20-minute fire resistance rating. 

•  In smoke-controlled doors. 

•  In doors that have a mineral core with reduced heat transfer. 

•  In fire-resistant doors for emergency exits, stairwells, or double-egress doors. 

•  In doors that have glazed openings. 

•  In fire-resistant Dutch doors. 

•  In fire-resistant transoms, fire-resistant skylights, or fire-resistant side panels. 

•  In many types of doors, like acoustic, lead-lined, and bulletproof doors. 

Maximum opening dimensions for fire doors: 

•  Single: 4’ x 10’ (1219 x 3048 mm) 

•  Double: 8’ x 10’ (2438 x 3048 mm) 

For more information, please consult:

•  NAAMM/HMMA 850-14 

•  NFPA 80 

•  SDI-118-01 

•  The National Building Code of Canada (NBC) 